BUILDING TELECOMMUNICATIONS DESIGN GUIDELINES

Indiana University, Bloomington

 

PURPOSE

This document is intended to serve as a guideline for architectural design as it pertains to telecommunications infrastructure on the Indiana University Bloomington Campus.  Greater detail is provided in the Division 25000 Telecommunications Specifications document for the Blooming Campus

 

GENERAL

Telecommunications and computing requirements as described herein for each area have been reviewed and approved by representatives of the technologies at both the campus and system levels.  However, these requirements are stated very generally.  For this reason and because of rapid changes in technology, University Information Technology Services Telecommunications and Networks staff must be actively involved in a review and advisory capacity from inception through construction. The design architect shall schedule regular design progress meetings with the University Information Technology Services Telecommunications Plant representative, a University Information Technology Services Network representative, and a university Engineering Services representative. These linkages shall be made through the University Architect’s Office and through commreq@indiana.edu.

 

Telecommunication system herein specified provides for voice, data, video and other low voltage signaling functions (such as for energy management and security systems) through twisted pair, fiber optic, and coaxial cable.  The system shall provide acceptable outlets for any telecommunication device, which requires connection to other devices, networks or information services serving general university needs.

 

Telecommunication design shall comply with Federal and State codes, regulations, and standards with variances adopted as standards by Indiana University and the State of Indiana.  Applicable state and national standards include: the latest National Electrical Code; Indiana Fire Prevention Code; REA Standards for Engineering, Construction, and Installation; FCC Rules and Regulations; National Electrical Safety Code; Joint Commission Accreditation of Hospitals Code; Life Safety Code; BICSI TDMM (Telecommunications Distribution Methods Manual); BICSI CO-OSP (Customer Owned Outside Plant Manual); ANSI/TIA/EIA/BICSI 568 (Commercial Building Telecommunications Cabling), ANSI/TIA/EIA/BICSI 569 (Commercial Building Standard for Telecommunications Pathways and Spaces), ANSI/TIA/EIA/BICSI 607 (Commercial Building Grounding and Bonding Requirements for Telecommunications), ANSI/TIA/EIA/BICSI 758 (Customer-Owned Outside Plant Telecommunications Cabling Standard), specifications as provided by University Information Technology Services Telecommunications and Network groups,

and other special codes that may apply.

 

 

TOPOLOGY

Horizontal cabling shall be installed in a star topology, with each work area communications outlet/connector connected to a horizontal cross-connect in a telecommunications room via the horizontal cable.

 

Station communications design is based on ‘one communications outlet per workstation’.  Therefore the components selected for an individual workstation communications outlet should reflect the needs of the intended and possible future users of a given outlet.

 

Due to the need to maintain a secure and manageable campus network, as well as the need to maintain location records of communication outlets and all equipment associated with them for E911 response databases, all equipment working from a given communications outlet must be located in the same room as the outlet. Communications data switching can under certain circumstances be supplied from an in-room switch hub to individual stations, or run back to a wiring closet via horizontal cabling (preferred). In-room hubs are allowed only for lab-type settings or temporary work clusters; large classrooms should be routed to Telecommunications Rooms.  A hub may not serve equipment in more than one room.  Any application of an in-room hub must be approved prior to design and implementation by the Indiana University Technology Services (UITS) Network group.  Those not approved will not be connected to the University data network. Further information on this topic may be obtained at http://www.itpo.iu.edu/IT19.html and http://www.itpo.iu.edu/IT20.html.

 

 

MAIN TELECOMMUNICATIONS ROOM

The primary function of the main telecommunications room is to house the necessary hardware to provide cross connection between the outside plant cables that enter the building from the campus communication distribution network and the inside backbone cabling. Room should be sized at a minimum of 100 sf with no dimension less than 7 feet.

 

The main telecommunications room may also serve as a building telecommunications room. If so, then the room should be sized at a minimum of 200 sf with no dimension less than 10 feet. If additional equipment, such as coaxial cable amplifiers and splitters are to be house in the room, then additional floor and wall space should be added according to the space requirements of that equipment and associated cabling and mechanical requirements.

 

The design must comply with ANSI/TIA/EIA-569 standard regarding the requirements and recommendations for separation of copper telecommunication cabling from sources of electromagnetic interference.

 

 

TELECOMMUNICATIONS ROOM

The primary function of a telecommunications room is the termination of horizontal and backbone cables to compatible connecting hardware, as well as splice closures, grounding and bonding facilities, and protection apparatus where applicable.

 

A telecommunications room also provides a controlled environment to house telecommunications equipment such as data networking electronic equipment, campus video, carrier equipment and, in the future, Voice Over IP equipment. The telecommunications room provides for the administration and routing of the equipment cables/cords from the horizontal cross-connect to the telecommunications equipment.

 

A telecommunications room should be sized at a minimum of 100 sf. If additional equipment, such as coaxial cable amplifiers and splitters are to be house in the room, then additional floor and wall space should be added according to the space requirements of that equipment and associated cabling and mechanical requirements.

 

The telecommunications room should be located on the same floor as and centrally located to the work areas served. In a large building, more than one telecommunications room may be necessary to keep horizontal cabling runs within the specified lengths.

 

All telecommunications rooms must be vertically stacked within multi-floor buildings.

 

If additional equipment, such as coaxial cable amplifiers and splitters are to be house in the room, then additional floor and wall space should be added according to the space requirements of that equipment and associated cabling and mechanical requirements.

 

The design must comply with ANSI/TIA/EIA-569 standard regarding the requirements and recommendations for separation of copper telecommunication cabling from sources of electromagnetic interference.

 

Additional requirements:

·        Minimum room height:  8'6"; no suspended ceiling

·        Horizontal cabling from mechanical termination at the communication outlet to mechanical termination in the serving equipment room not to exceed 295 ft.

·        Control of heat and humidity essential, to be maintained between 32oF and 100oF and between 15%RH and 95%RH non-condensing.  Current network equipment generates 341.25 btu per 24 data ports installed; design cooling to maximum number of current and future data ports that can be installed, in addition to other heat generating equipment to be installed in the telecommunications room.

·        Minimum door dimensions:  36"w and 80"h

·        Campus telecommunications personnel shall approve key/locking arrangements; Telecommunications Room and Main Telecommunications Room key sets should be the same.  Telecommunications Room key cores shall be included as part of the project.

·        Compact fluorescent lighting with a minimum of two fixtures; provide duplex outlet(s) for task lighting

·        Do not locate near alternating current (AC) switch gear as defined in NEC Article 110 and referenced sections.

·        Two 120v 20 amp circuits with four duplex outlets (surge suppression type) on each circuit; isolate these feeds from motors, AC switch equipment, lighting circuits; minimum noise and interference

·        The riser system (Main Telecommunications Room to each Telephone Room) will contain Category 3 shielded UTP for voice, fax and modem use; Category 6 data risers for Network use; fiber optic cable for data and video use; and possibly coaxial cable for video use.  The amount of each type cannot be stated until the design stage of the riser system.

·        Room should be clear of mechanicals such as ventilation ducts, water, sewer, or steam pipes, and high voltage electric

·        4' x 8' plywood backboard, 3/4" thick, painted with a light colored fire retardant paint, shall be mounted 4" AFF on all walls.

·        Three (3) equipment racks with vertical wire management, 7' high and to accommodate 19" bay-mounted equipment in each telecommunications room.  Equipment racks must be attached to floor with an overhead runway to a wall.  Additionally there should be a 12” cable runway mounted to top of equipment racks and the wall where the copper terminations are installed.  Equipment racks must be attached to floor with an overhead runway to a wall.  All equipment racks and raceways shall be bonded per NEC. 

·        Cable tray above frame to accommodate cabling to the plywood backboard; cable tray to surround room at a minimum height of 7' 2"AFF from the bottom of the tray, and with a minimum clearance of 12” above the tray; cable tray to be 12" by 5" ladder type (with water falls at cable exit points) with 18" tray extending in room.  Include a section of 12" ladder rack extending from the cable tray to each individual equipment rack

·        Outlet boxes 4" x 4" with 5/8" 2-gang plaster ring connected to 1" conduit stubbed out to within 3" above cable tray

·        A TGB (Telecommunications Ground Busbar) shall be located in each Telecommunications Room and shall be tied back to the TMGB (Telecommunication Main Busbar located in Main Telecommunications Room) with a minimum of a number 6 copper bonding conductor TBB (Telecommunications Bonding Backbone). The minimum dimensions of the TGB are .25” thick, 2” wide, and variable length. The minimum dimensions for the TMGB is .25” thick, 4” wide and variable length. Both should be insulated from their support.

 

PATHWAYS

The size of the telecommunications raceway system and station device box are defined in the specifications and are such that they will accommodate all of the telecommunication services available. 

 

The pathways and spaces shall be designed and installed to support horizontal cabling in accordance with the requirements of ANSI/TIA/EIA-569-A.

 

 

BACKBONE CABLING

Cabling from the Main Telecommunications Room to each Telecommunications Room is considered as riser cable.

 

Splices in backbone cable runs are not permitted.  Wiring must be continuous from connecting block to connecting block.

 

The intra-building cabling and the riser cabling shall be in agreement with ANSI/TIA/EIA-568 Category 3 requirements.

 

 

HORIZONTAL CABLING

The horizontal cabling is the portion of the telecommunications cabling system that extends from the work area telecommunications outlet/connector to the horizontal cross-connect in the telecommunications room. The horizontal cabling includes horizontal cables, telecommunications outlet/connectors in the work area, and mechanical terminations.

 

In addition to satisfying today's telecommunications requirements, the horizontal cabling should be planned to reduce on-going maintenance and relocation. It should also accommodate future equipment and service changes. After construction of the building, the horizontal cabling is often much less accessible than the backbone cabling. The time, effort, and skills required for changes can be extremely high. In addition, access to the horizontal cabling frequently causes disruption to occupants and their work. These factors make the choice and layout of horizontal cable types very important to the design of the building cabling. Consideration should be given to accommodating a diversity of user applications in order to reduce or eliminate the probability of requiring changes to the horizontal cabling as user needs evolve.

 

The horizontal distance is the cable length from the mechanical termination of the media at the horizontal cross-connect in the telecommunications room to the terminations on the telecommunications outlet/connector in the work area. The maximum horizontal cable distance shall be 90 m (295 ft), independent of media type. Any horizontal station wiring run longer than this will not be accepted by the University. Splices in horizontal cable runs are not permitted.  Wiring must be continuous from outlet to connecting block.

 

 

COMMUNICATION OUTLETS

A communication outlet as described below and used in this document is defined as "providing access to all available communication media:  twisted pair, coaxial cable, and in the future fiber.  Thus voice and data are the basics of an outlet; if optional video and fiber optic services are required, they shall be so indicated in individual room or area descriptions.

 

The maximum horizontal cable length is based on a maximum length of 5 m (16 ft) of work area cord.  Therefore no communication outlet will be installed such that the intended workstation or device cannot be reasonably reached by a 16 ft cord.

 

Communications outlet assemblies shall be located in fully accessible, permanent locations such as building columns and permanent walls. Multi-user telecommunications outlet assemblies shall not be located in ceiling spaces or any obstructed area.

 

Gang assemblies will require 2-1/8” deep boxes to accommodate the jack assemblies and bending radius of horizontal wiring.

 

Communications Outlet Types at IUB

 

STANDARD JACK:  One Category 5 station cable terminated to one (1) Category 5 RJ-45 jack for voice, and one Category 6 station cable terminated on one (1) Category 6 RJ-45 jack for data in a single gang configuration installed at the same height as 120 volt AC outlets (normally 18" above finished floor).

 

Advanced User Jack:  One Category 5 station cable split between two (2) Category 5 RJ-45 jacks for voice, and two Category 6 station cables terminated on two (2) Category 6 RJ-45 jacks for data in a single gang configuration installed at the same height as 120 volt AC outlets (normally 18" above finished floor). 

 

ATM Jack:  Two Category 5 station cables terminated on two (2) Category 5 RJ-45 jacks in a surface mount box.

 

Card Reader Jack:  One Category 5 station cable terminated to one (1) Category 5 RJ-45 jack for voice in a single gang configuration (no data).

 

Classroom Jack:  One Category 5 station cable terminated on one (1) Category 5 RJ-45 jack for voice, four Category 6 station cables terminated on four (4) Category 6 RJ-45 jacks for data, and one RG-6 coax with “F” connector termination, in a triple gang configuration (one gang for voice-data, one gang for coax, and one blank gang for future media).

 

Data-Only Jack:  One or more Category 6 station cables terminated on individual Category 6 RJ-45 jacks for data.  The number of RJ-45 connectors and gang-size configuration must be determined for individual applications; more than one data-only configuration is likely when classrooms, work areas, and offices are contained in the same building.

 

Elevator Phone Jack:  One Category 5 station cable terminated to an RJ-11 or RJ-45 surface mount biscuit jack, mounted in outlet box adjacent to elevator control box.

 

Emergency Phone Jack:  One Category 5 station cable (inside building) or one multi-pair buried drop (outside, protected) terminated on an RJ-11 or RJ-45 surface mount biscuit jack, mounted inside of phone base.

 

Multiple User Jack:  Various configurations are possible for special concentrations of users.  Consult with UITS Telecommunications for special applications and designs.

 

Payphone Jack:  One Category 5 station cable to be terminated directly to payphone equipment. A non-ADA compliant pay telephone jack requirements are the same as for a wall mounted telephone except the outlet box is positioned 48" A.F.F. to the center of the outlet box. The ADA compliant pay telephone requirements are the same as for a wall mounted telephone except the outlet box is positioned 42" A.F.F. to the center of the outlet box and requirement for AC outlet.

 

Security Jack:  One Category 5 station cable terminated on one (1) RJ-31X jack for voice, and one Category 6 station cable terminated on one (1) Category 6 RJ-45 jack for data in a single gang configuration.  This configuration is for Ademco alarms.

 

Wall Jack:  One Category 5 station cable terminated on one (1) RJ-45 jack for voice.  Wall mounted telephones require a special wall telephone jack that provides mounting lugs for the telephone and an eight position jack.  The outlet box for this installation is a 2 gang box with a single gang plaster ring and will be positioned 54" A.F.F. to the center of the outlet box.

 

 

DESIGN DRAWINGS

Design drawings shall include, but not be limited to:

            Backbone cable routing diagrams

            Backbone cable schematic diagrams, including cable sizes

            Telecommunication room locations

            Telecommunication room layouts

            Telecommunication room details

            Conduit / cable tray routing, elevations in relation to other mechanicals

and building structures, sizes, and pull box and access point locations

            Other supporting structures for telecommunications cabling

            Grounding schematic for telecommunications rooms

 

 


Last updated:  September 10, 2002
URL:  http://www.indiana.edu/~classrms/telecomguidelines.html
Comments to: UITS
Copyright 2002-2003, the Trustees of Indiana University